Capacity controller
EKC 331T
REFRIGERATION AND
AIR CONDITIONING
Manual
Introduction
Application
Thecontrollerisusedforcapacityregulationofcompressorsor
condensersinsmallrefrigeratingsystems.
Regulationcanbecarriedoutwithuptofouridenticalcapacity
steps.
Advantages
•Patentedneutralzoneregulation
•Sequentialorcyclicoperation
Functions
•Regulation
Regulationwithuptofourrelayoutputscanbecarriedout.
Regulationtakesplacewithasetreferencewhichiscompared
toasignalfromapressuretransmitteroratemperaturesensor.
•Relaymodule
Itispossibletousethecontrollerasrelaymodule,sothatthe
relaysarecutinoroutbymeansofanexternalvoltagesignal.

Alarmfunction
Arelaybecomesactivatedwhenthesetalarmlimitsareex-
ceeded.

Digitalinput
Thedigitalinputcanbeusedfor:
-nightoperationwherethesuctionpressureisraised
-heatrecoverywherethecondensingpressureisraised
-externalstart/stopoftheregulation.
-Monitoringofsafetycircuit
•Possibilityofdatacommunication
Display
Asignalfromapressuretransmitterwillalwaysbeconvertedand
shownasatemperaturevalue.
Settingsaremadeasfortemperaturevalues.
Function
Capacity regulation
Thecut-incapacityiscontrolledbysignalsfromtheconnected
pressuretransmitter(temperaturesensor)andthesetreference.
Outsidethereferenceaneutralzoneissetwherethecapacitywill
neitherbecutinnorout.
Outsidetheneutralzone(inthehatchedareasnamed+zoneand
-zone)thecapacitywillbecutinoroutiftheregulationregisters
achangeofpressure(thetemperature)“away”fromtheneutral
zone.Cutinandcutoutwilltakeplacewiththesettimedelays.
Ifthepressure(thetemperature)however“approaches”the
neutralzone,thecontrollerwillmakenochangesofthecut-in
capacity.
Ifregulationtakesplaceoutsidethehatchedarea(named++zone
and--zone),changesofthecut-incapacitywilloccursomewhat
fasterthanifitwereinthehatchedarea.
Cutinofstepscanbedeinedforeithersequentialorcyclicopera-
tion.
Manual RS8CU40 © Danfoss 05-006
EKC331T
 Sequential
Therelaysareherecutininsequence–irstrelaynumber1,then
,etc.
Cutouttakesplaceintheoppositesequence,i.e.thelastcut-in
relaywillbecutoutirst.
Cyclic
Therelaysarecoupledheresothattheoperatingtimeofthe
individualrelayswillbecomeequalised.
Ateachcutintheregulationscanstheindividualrelays’timer,
cuttingintherelaywithleasttimeonit.
Ateachcutoutasimilarthinghappens.Heretherelayiscutout
thathasmosthoursonthetimer.
Rx=randomrelay
h=numberofhours
Ifcapacityregulationiscarriedoutontwocompressorswithone
unloadereach,thefollowingfunctioncanbeused:
Relays1and3areconnectedtothecompressormotor.
Relaysand4areconnectedtotheunloaders.
Relays1and3willoperateinsuchawaythattheoperatingtime
forthetworelayswillbecomeequalised.
C=compressor,L=Unloader
Relay module
Thecontrollercanalsobeusedasarelaymodulewheretherelays
inthemoduleareoperatedbythereceivedvoltagesignal.The
signalmustbeconnectedtoterminal15-16.
Dependingonthedeinitionofthesignalandthenumberof
relaysused,therelayswillbe”distributed”overthesignal.
Ahysteresisattheindividualcouplingpointswillensurethatthe
relaywillnotcutinoroutwhennotrequired.
EKC331T
Manual RS8CU40 © Danfoss 05-006
3
 Suvey of functions
Function
Para-
meter
Parameter by operation via
data communication
Normal display
Normallythesignalfromthepressuretransmitter/temperaturesensorisshown
Ifthecontrollerisusedasrelaymodule,U
in
willappearonthedisplay.
Pressure/Temp°C
Pressure regulation
Reference
Regulation setpoint
Regulationisbasedonthesetvalue.
Achangeofthesetvaluecanbelimited/ixedbymeansofthesettingsinr0andr03.
(Pushbothbuttonssimultaneouslytosetthemenu.)
-
Setpoint°C
Neutral zone
Thereisaneutralzonearoundthereference.Seealsopage.
r01
Neutralzone
R
eference
Thesetreferencemaybedisplacedwithaixedvaluewhenasignalisreceivedatthe
DIinput.Regulationwillthenbebasedonthesetpointplusthevaluesethere.
(Cf.alsoDeinitionofDIinput).
r13
OfsetK
Thetotalreferencecanbeseenwhenyoupushthelowerofthetwobuttons
-
Reference
Set point limitation
Thecontroller’ssettingrangeforthesetpointcanbenarroweddown,sothatyou
cannotaccidentallysetatoohighortoolowvalue-thatmayresultindamagetothe
system.Withthesesettingsthesetpointcanonlybesetbetweenthetwovalues.
Max.permissiblesetpointvalue.
r0
Max.setpoint
Min.permissiblesetpointvalue.
r03
Min.setpoint
Correction of temperature measurement
Anofsetadjustmentoftheregisteredtemperaturecanbemade.Thefunctionisused
ifcorrectionforatoolongsensorcablehastobemade.
r04
Adjustsensor
Unit
Hereyoucanselectwhetherthedisplayistoindicatetemperaturesin°Corin°F.
Setting="C-b"willgive°C.
Setting="F-P"willgive°F.
r05
Unit
0:°C
1:°F
(InAKMonly°Cisused,whateverthe
setting)
Capacity
Capacity
Running time
Topreventfrequentstart/stop,valueshavetobesetforhowtherelaysaretocutin
andout.
Min.ONtimeforrelays.
c01
Min.ONtime
Min.timeperiodbetweencutinofsamerelay.
c07
Minrecycletime
Coupling
Cutinandcutoutcantakeplaceinthreeways:
1.Sequential:Firstrelay1cutsin,thenrelay,etc.Cutouttakesplaceintheopposite
sequence.(”Firstin,lastout”).
.Cyclic:Anautomaticoperatingtimeequalisationisarrangedhere,sothatallsteps
willhavethesameoperatingtime.(Therelaywiththefewestnumberofoperating
hourscutsinoroutbeforetheothers)(Orputdiferently:”Firstin,lastout”).
3.Cyclicwithunloader:Thefunctioncanonlybeusedwhentherearetwocompres-
sorswithoneunloadereach.Thecyclicoperationisperformedonrelays1and3.The
unloadersaremountedonrelaysand4(relays1andbelongtotheirstcompres-
sor,relays3and4totheother).Theabovementioned”Min.On-time”and"Min.
recycletime"arenotusedforunloaders.
Inconnectionwithcutout,thetwounloadersarecutouteforethecompressorsare
cutout.
c08
Stepmode
Unloaders’ cutin and cutout mode
(Onlyinconnectionwithcutin/cutoutmode3.Seeabove).
Therelaysforthetwounloaderscanbesettoswitchonwhenmorecapacityisre-
quired(setting=no),ortheycanswitchofwhenmorecapacityiscalledfor(setting
=nc).
c09
Unloader
(switchon=0)
(switchof=1)
4
Manual RS8CU40 © Danfoss 05-006
EKC331T
Setting for neutral zone regulation
Regulationbandundertheneutralzonen
c10
+ZoneK
Timedelaybetweenstepcut-insintheregulationbandovertheneutralzone
c11
+Zonem
Timedelaybetweenstepcut-insintheregulationbandoverthe"+Zoneband".
c1
++Zones
Regulationbandovertheneutralzone
c13
-ZoneK
Timedelaybetweenstepcut-outsintheregulationbandundertheneutralzone
c14
-Zonem
Timedelaybetweenstepcut-outsintheregulationbandunderthe"-Zoneband"
c15
--Zones
Alarm
Alarm settings
Thecontrollercangivealarmindiferentsituations.Whenthereisanalarmallthe
light-emittingdiodes(LED)willlashonthecontrollerfrontpanel,andthealarmrelay
willcutin.
Upper deviation
Hereyousetwhenthealarmathightemperature/pressureistoenterintoefect.The
valueissetasanabsolutevalue.
Seealsoemergencyprocedurepage7.
A10
Max.press/Temp.
Lower deviation
Hereyousetwhenthealarmatlowtemperature/pressureistoenterintoefect.The
valueissetasanabsolutevalue.
Seealsoemergencyprocedurepage7.
A11
Min.press/Temp.
Alarm delay
Ifoneofthetwolimitvaluesisexceeded,atimerfunctionwillcommence.Thealarm
willnotbecomeactiveuntilthesettimedelayhasbeenpassed.Thetimedelayisset
inminutes.
A03
Alarmdelay
Givethetopbuttonabriefpushtozerosetthealarmandtohavethemessageshown
onthedisplay.
Resetalarm
Thefunctionzerosetsallalarmswhen
setinpos.ON.
Alarmrelay
Hereyoucanreadthestatusofthe
alarmrelay.
(ONindicatesoperationwithalarm).
Withdatacommunicationtheimpor-
tanceoftheindividualalarmscanbe
deined.Settingiscarriedoutinthe

Alarm destinations
”menu.
Miscellaneous
Miscellaneous
External signal
Hereyousetthesignaltobeconnectedtothecontroller.
0:Nosignal/regulationstopped(displaywillthenshowOFF)
1:4-0mAfrompressuretransmitterforcompressorregulation
:4-0mAfrompressuretransmitterforcondenserregulation
3:PressuretransmittertypeAKS3Rforcompressorregulation
4:PressuretransmittertypeAKS3Rforcondenserregulation
5:0-10Vfromotherregulation
6:0-5Vfromotherregulation
7:5-10Vfromotherregulation
8:Pt1000ohmtemperaturesensorforcompressorregulation
9:Pt1000ohmtemperaturesensorforcondenserreguation
10:PTC1000ohmtemperaturesensorforcompressorregulation
11:PTC1000ohmtemperaturesensorforcondenserregulation
o10
Applicationmode
Number of relays
Dependingontheapplication,uptofourrelaysmaybeused.Thisnumbermustbe
setinthecontroller.(Therelaysarealwaysusedinnumericalsequence).
o19
Numberofsteps
Pressure transmitter’s working range
Dependingonthepressure,apressuretransmitterwithagivenworkingrangeis
used.Thisworkingrangemustbesetinthecontroller(e.g.:-1to1bar
Thevaluesmustbesetinbarifdisplayin°Chasbeenselected.Andinpsig,if°Fhas
beenselected.
Ifthetwovaluesaretobesetfromthe
AKMprogramme,theymustbesetin
bar.
Min.value
o0
Min.trans.press
Max.value
o1
Maxtrans.press
EKC331T
Manual RS8CU40 © Danfoss 05-006
5